POWER UNIT UNLOADING DUE TO THE THIRD MAIN CIRCULATION PUMP (MCP-3) TURNING-OFF AS A RESULT OF FALSE OPERATION OF MAJOR PROTECTION SYSTEM

On April 19, 19992 at 08:58 a.m. while unit 4 was running at rated power a fire-alarm signal emerged indicating a fire in make-up pumps oil systems compartment. The fire-fighting system pumps were actuated. Inspection of the compartment revealed neither ignition nor fume therefore the pumps were turned off.
When removing the cause of the signal malfunction, owing to a maintenance personnel mistake the fire-fighting system gate valves in the MCP-3 oil system compartment had accidentally been opened and water ingressed to MCP-3 oil system sensing elements. The latter caused a false signal of rise in oil pressure at MCP-3 and it was turned off. The reactor unit got automatically unloaded to 67% of the level of power permitted for three MCPs when sensing elements troubles were removed MCP-3 was turned on and on April 20, 1992 at 14:10 the unit rated power was restored.

Location: ZAPOROZHE-4
Event date: Sun, 19-04-1992